	As a Zone 2-Category 3 device, the PC3-6224 Ethylene Oxide gas detector is designed for continuously monitoring Ethylene Oxide in the light industrial areas.
 High-quality catalytic sensor in PC3-6224 shows excellent results in 0-20ppm range.
• Sensor: Uses high-quality electrochemical sensor to detect Ethylene Oxide gas in 0-20ppm range.
• Connection: Provides universal output 4-20mA and Modbus RS485
• Entry: 1 x 1/2″ NPT cable entry
• Body: Aluminium die-cast body and sensor head superb performance under harsh environmental conditions with IP65 protection class.
• Remote Control: Detector status can be monitored through Prosense Gas Monitoring software remotely.
• Modbus: Easy to integrate into SCADA systems via open-source Modbus RS485(RTU) codes
• Relay Contacts: 2 Alarm, 1 Fault relays can be set predefined levels and they can manage the other devices like a siren, a beacon in case of any event.
		 
	| Sensor Technology | Electrochemical | 
| Output Signal | 4-20mA Analog Modbus RS485 RTU | 
| Sensor Warm-Up | 60sec | 
| Response Time(T90) | <30sec | 
| Accuracy | %±1 | 
| Operating Temperature | ‐20°C ~ +50°C | 
| Humidity | 5 ~ 95%RH Non-Condensing | 
| Input | Min 10VDC - Max 32VDC - Nominal 24VDC | 
| Power Consumption | Max.2W | 
| Relay Outputs | 2 Alarms (Selectable), and 1 Fault (All relays are NO/NC adjustable) | 
| Cable Entry | 1x 1/2"NPT | 
| IP Rating | IP65 | 
| Junction Box | Epoxy Painted Die‐cast Aluminium | 
| Sensor Head | Nickel‐plated Brass | 
| Dimensions/Weight | 230x120x100mm / 1100gr | 
| Standards | EN 60079‐0 EN 60079‐1 EN 60079‐18 | 
| Hazardous Class | Zone 2 ‐ Category 3 | 
 
                 
					 
					 
					 
	

 
				 
				 
				 
				 
				 
				
PC3 Datasheet
PC3 User Manual